Troubleshooting the
RV DSI Furnace
The following descriptions are based on the
Hydro Flame 8500 series furnaces, but the operating
principles are similar for other
manufacturers.
Low Battery
Voltage
The furnace is designed to operate at voltages
between 10.5 to 13.5 VDC. Low voltage will not run the
blower motor at the proper speed to commence the ignition
sequence. This is a safety feature that ensures the
blower will be able to provide enough combustion air to
operate the burner at it's designed
efficiency.
Obstructed return air
intake
Return air is the air that flows in to replace
the heated air that the blower pushes out through the
ducting. This air is pulled in by the furnace through
louvered openings in the side of the furnace cabinet, and
any items stored near these openings could interfere with
this air flow.
Obstructed exhaust
The exhaust venting must be clear of all
obstructions for proper furnace operation. Inspect the
vents for insect or bird nests or other
debris.
Low gas pressure
Low gas pressure will affect a burner in several
ways. When a malfunctioning burner is encountered, the
first step is to make sure the gas pressure is
correct.
Gas pressure to a propane fueled appliance
should be 10.5 to 11 inches of water column pressure.
This is controlled by the main system
regulator.
Time delay
relay
This relay performs two separate jobs - one to
handle the relatively high current needed to run the
blower motor - and two, to allow the blower to run for 45
to 90 seconds after the thermostat is satisfied. This
allows excess heat in the chamber to disipate before the
blower stops.
The relay is normally open and should always
have power from the circuit breaker. Only when power from
the thermostat is present does the relay close after a 20
second delay. Power then flows to the blower motor. Newer
models have a relay built into the circuit board and do
not use this relay.
Blower motor
Next in the ignition sequence is the blower
motor. It drives two squirel cage fans to provide
separate air flow for the combustion process and for
distributing the heated air to the coach. A heat
exchanger is used to separate the heat from the burning
gas while preventing exhaust gases from entering the
living space.
Sail switch
The sail switch (air prover switch) is an on/off
device. (normally in the off position) It gets it's name
from the "sail" or paddle that is attached to the switch
mechanism. As the blower comes up to speed, it blows air
onto the sail with enough force to push the switch
closed, thus allowing electrical current to flow to the
next component in line.
It's job is to determine if there is adequate
air flow for proper combustion to take place. If the
battery voltage is low or the fan does not come up to 75
per cent of it's design speed, the sail switch will not
close.
Possible causes of this malfuntion are: low
battery, restricted return air inflow, restricted or
inadequate outlet vents, restricted combustion air inlet
or exhaust, faulty sail switch or faulty blower
motor.
Limit switch
The limit switch is a simple temperature
controlled switch. It's function is to monitor the
combustion chamber heat level. If the temperature of the
combustion chamber exceeds the preset limit, the switch
will open and disrupt the flow of current to the circuit
board, in effect, shutting down the main burner. Once the
chamber temperature cools sufficiently, the limit switch
resets. This initializes the ignition sequence and starts
another cycle. This condition is referred to as
"limiting".
Circuit board
The circuit board will not recieve power until
the sail switch is closed by adequate air flow from the
blower. The power must also flow through the limit
switch.
When the circuit board is triggered by this
current, it delays ignition for about 15 seconds to allow
the blower to purge the combustion chamber of any
unburned gases.
The circuit board then sends high voltage pulses
to the electrode assembly, providing a series of sparks
to ignite the gas/air mixture.
At the same time, the circuit board sends power
to open the gas valves allowing the fuel to flow to the
burner.
If everything is okay, the main burner
ignites.
The circuit board monitors the burn cycle
through a sensor that detects the presence of the flame.
If the sensor does not detect a satisfactory flame within
about 10 seconds, the board then shuts off the gas valves
and discontinues the ignition spark.
Depending on the board design, it will try for
ignition up to three times. Beyond that point, it goes
into lockout mode, will not retry for ignition until
reset and the blower will continue to run.
Burner
assembly
This illustration shows the burner assembly for
the Hydroflame 8500 series furnace.
Many older furnaces used a very different burner
configuation, but the principles remain the
same.
The burner needs an ignition source (pilot or
electronic spark), an appropriate combustion air supply,
and proper fuel metering (orifice) to operate at it's
designed capacity.
Electrode
assembly
Electrodes are designed to provide an ignition
spark - to initiate the burn - and to provide feedback to
the circuit board when the flame is established. The
propane flame creates a tiny electrical current which is
sensed though the electrode assembly. This current is
sent back to the circuit board, which in turn, decides if
the flame is adequate. If not, the circuit board will
shut down the burner.
The electrode assembly may have two or three
probes, depending on the furnace make and model. Some
systems used the extra probe for a ground circuit, others
incorporated the ground circuit into the second probe. In
any case, the gap between the spark probe and the ground
(or other probe), should be 1/8 inch.
The electrodes must be clean and free of carbon
or other deposits. Do not file or sand the surfaces as
you will damage the protective coating and shorten the
electrode life. Simply wipe off the contacts with a cloth
and solvent, and replace them if needed.
Thermostat

The thermostat is an on/off switch controlled by
a bi-metal coil that senses the changes in temperature
and opens or closes an electrical contact. This signal is
sent to the furnace to start or stop the heating
cycle.
|